You signed in with another tab or window. Reload to refresh your session.You signed out in another tab or window. Reload to refresh your session.You switched accounts on another tab or window. Reload to refresh your session.Dismiss alert
Use this reference to look up fields while editing engine configuration. The
configuration specification defines validation, apply behavior,
path syntax and transformation rules in full.
bootstrap.json is read at engine start; restart after editing it. runtime.json is
versioned and applied through the console or CLI. Unknown fields are rejected. Both files
are UTF-8 JSON without comments. Durations use the unit in their name; sizes are bytes
unless named _megabytes. Relative bootstrap paths resolve beside bootstrap.json.
In the tables, required means no default, assigned means the engine supplies it,
and null is allowed only where shown. IDs match ^[a-z0-9][a-z0-9._-]{0,63}$; labels
contain 1–100 characters. Keep IDs stable. Settings fields are relative to their named
object, rather than complete JSON paths.
Bootstrap
Field
Default
Value or purpose
schema_version
1
Integer; supported schema version.
node.node_id
Required
ID; also used in the Windows pipe name.
node.display_name
Required
Display label.
node.environment
prod
dev, test, prod.
node.site_id
null
Optional string, at most 100 characters.
paths.state_directory
Required
Creatable, writable directory for stored messages, versions and IPC socket.
paths.log_directory
<state_directory>/logs
Creatable, writable directory.
ipc.path
null
Default: <state_directory>/packie.sock on Unix or \\.\pipe\packie-<node_id> on Windows. Custom Unix socket path: at most 100 bytes.
ipc.group
packie
Management access group on every platform. Unix: socket mode 0660 for the group. Windows: packie means local PACK-IE Operators; another name selects a local/domain group besides SYSTEM and Administrators. null or a missing group leaves service/administrator access only (Unix 0600); a missing group logs ipc.group_unavailable. Empty string is invalid.
hosting.shutdown_drain_seconds
15
Integer, 1–300; host stop timeout must allow at least this long.
runtime.file
<state_directory>/runtime.json
Runtime document; parent directory must be writable.
runtime.versions_kept
null
Keep all versions; otherwise a positive integer limits the count, preserving versions younger than audit.retention_days. Includes change records/sign-offs.
logging.level
info
error, warn, info, debug, trace.
logging.retention_days
30
Integer, 1–3650.
logging.rotate_at_megabytes
64
Integer, 1–1024; logs also rotate at local midnight.
logging.ring_buffer_events
20000
Integer, 1000–1,000,000; live in-memory log capacity.
diagnostics.snapshot_interval_seconds
1
Integer, 1–60.
diagnostics.retain_recent_errors
100
Integer, 10–10,000 per channel.
secrets.provider
keystore (macOS, Windows); file (Linux)
keystore or file. On Linux keystore needs a Secret Service (desktop session); without one the engine refuses to start and names file. The Linux package sets file.
secrets.file
<state_directory>/secrets.json with provider=file
Secret-store file path; created owner-only on the first secret write; on Unix, group and others must have no permission bits.
audit.retention_days
2190
Integer, 365–36,500. Removes whole sealed yearly audit files only after their newest event ages out; records the removal. Keep at least as long as the longest message retention and the lab's required calendar interval.
backup.directory
Not set
Backup root; required with a schedule. Each default/scheduled backup uses a new packie-backup-<UTC time> directory. Use an encrypted volume writable by the service account.
backup.schedule
null
No automatic backup; otherwise an object with daily_at and optional keep below.
backup.schedule.daily_at
Required with schedule
Local time HH:MM, daily. A time skipped by daylight saving runs at the next valid instant.
backup.schedule.keep
7
Integer, 1–365. After a scheduled backup, retain this many newest complete packie-backup-* directories; other names and pre-restore copies are untouched.
backup.stale_after_hours
26 with schedule, otherwise null
Integer, 1–8760; backup_stale warns when the newest successful backup exceeds this age, or no backup succeeds within this interval after start. null without a schedule turns it off.
notifications.rate_limit_minutes
15
Integer, 1–1440; one notification per alert code/channel/endpoint/destination in this interval, shared by targets and by raise/clear events.
notifications.ca_file
null
Optional path to a PEM CA certificate bundle, read at startup; a relative path resolves against the bootstrap file's directory. SMTP adds these roots to bundled Mozilla roots; HTTPS webhooks use only this bundle when set. Unreadable/invalid bundles fail TLS sends.
notifications.email
null
SMTP target object; null disables e-mail.
notifications.email.host
Required with e-mail
Non-empty relay host name or address.
notifications.email.port
Required with e-mail
Integer, 1–65535.
notifications.email.security
starttls
starttls (usually 587), tls (usually 465) or none. none is allowed only for localhost, 127.0.0.1 or ::1. TLS verifies the relay certificate against bundled Mozilla roots plus notifications.ca_file when set.
Optional login; set both together. Password must be a secret reference, such as {"secret":"smtp-password"}.
notifications.email.from, notifications.email.to
Required with e-mail
Sender address and non-empty array of recipient addresses; each address needs one @ with text on both sides, without spaces or angle brackets.
notifications.email.severities
["warning","critical"]
Non-empty subset of warning and critical.
notifications.webhook
null
Webhook target object; null disables it.
notifications.webhook.url
Required with webhook
HTTPS URL without a user name; HTTP allowed only for localhost, 127.0.0.1 or [::1]. Bundled Mozilla roots verify HTTPS certificates unless notifications.ca_file is set (then only that bundle is trusted); redirects are not followed.
notifications.webhook.bearer
null
Optional secret reference sent as Authorization: Bearer <secret>.
notifications.webhook.severities
["warning","critical"]
Non-empty subset of warning and critical.
notifications.webhook.timeout_seconds
10
Integer, 1–60; time to connect and receive the response.
test_hooks
false
Boolean; scenario hooks. Never enable in production.
Backup paths resolve relative to the bootstrap directory like other bootstrap paths. See
backup setup and restore and audit behavior.
Notifications are off without targets. See
notification relay setup for private-CA installation and
service-account file access.
Keep node/channel/endpoint labels free of patient information because notifications include them.
See notification behavior and tests.
Apply notes and verification references belong to commands, not fields in runtime.json:
packie config apply <file> --note "Reason" and
packie config verify <version> --note "Validation record reference" require 1–500 characters.
Runtime envelope and diagnostics
Field
Default
Value or purpose
schema_version
1
Integer; supported schema version.
config_version
Assigned
Successful apply increments the version. CLI apply uses an exported value to detect conflicting edits; it is not the new version number.
generated_at
Assigned
ISO-8601 UTC save time; informational.
diagnostics
{}
Overrides below.
alerts
{}
Thresholds below.
endpoints
[]
Endpoint definitions.
channels
[]
Channel definitions.
diagnostics.snapshot_interval_seconds
Bootstrap value
Integer, 1–60.
diagnostics.retain_recent_errors
Bootstrap value
Integer, 10–10,000 per channel.
Alert thresholds
All fields belong to runtime alerts and take integers. Zero disables only the thresholds
marked “off”.
Field
Default
Range and alert
endpoint_down_seconds
60
1–86,400; endpoint-down warning.
endpoint_down_critical_seconds
900
At least endpoint_down_seconds; endpoint-down critical.
no_peer_seconds
0 (off)
0–86,400; no peer connected.
buffer_high_percent
80
1–100; bridge buffer pressure level.
buffer_high_seconds
10
1–3600; bridge buffer pressure duration.
delivery_backlog_count
1000
0–10,000,000 (0 off); queued delivery count.
delivery_backlog_age_seconds
300
0–604,800 (0 off); oldest queued delivery age.
delivery_attention_critical_count
10
1–10,000,000; deliveries needing attention become critical.
invalid_messages_count
5
0–10,000 (0 off); invalid messages in the window.
invalid_messages_window_seconds
600
1–86,400; invalid-message counting window.
disk_low_megabytes
1024
1–10,000,000; low-disk warning.
disk_critical_megabytes
256
1–disk_low_megabytes; low-disk critical.
Endpoints
Fields below belong to each entry in runtime endpoints. Kind-specific fields belong to
that endpoint's settings.
Common field
Default
Value or purpose
endpoint_id
Required
ID unique among endpoints.
label
Required
Display label.
enabled
true
Boolean; false prevents opening the endpoint.
kind
Required
serial, tcp_client, tcp_listener, folder, sftp.
settings
Required
Object for the chosen kind.
tags
{}
Up to 20 string-to-string metadata entries.
Serial settings
Field
Default
Value or purpose
port_name
Required
Device path or COM port; unique among enabled endpoints, ignoring case.
baud_rate
Required
Integer greater than 0.
data_bits
8
5, 6, 7, 8.
parity
none
none, even, odd.
stop_bits
one
one, two.
flow_control
none
none, rts_cts, xon_xoff.
read_timeout_ms
1000
Integer, 1–60,000; read polling window, not a disconnect deadline.
write_timeout_ms
1000
Integer, 1–60,000; expiry fails the write attempt.
virtual_link
null
Unix pseudo-terminal path. When set, port_name must be virtual.
TCP settings
Field
Kind
Default
Value or purpose
host
tcp_client
Required
Host name, IPv4 or IPv6 literal.
bind_address
tcp_listener
Required
IPv4 or IPv6 literal.
port
Both
Required
Integer, 1–65535. Enabled listener binds must not overlap on the same port.
connect_timeout_ms
tcp_client
5000
Integer, 1–120,000.
accept_backlog
tcp_listener
16
Integer, 1–1024.
allowed_peer_cidrs
tcp_listener
[]
IPv4/IPv6 CIDR strings; restrict accepted peers.
allow_any_peer
tcp_listener
false
Boolean; explicitly set true to allow a non-loopback listener with no allowlist. Ignored with a non-empty allowlist.
idle_timeout_seconds
Both
0
Integer, 0–604,800; 0 disables. Closes a connection idle in both directions.
keep_alive
Both
true
Boolean; listener applies it to accepted sockets.
keep_alive_time_sec
Both
30
Integer, 1–7200; idle time before first probe.
keep_alive_interval_sec
Both
10
Integer, 1–3600; interval between probes.
keep_alive_retry_count
Both
3
Integer, 1–100; unanswered probes before failure.
Probe settings apply when keep_alive=true. Older Windows hosts without probe tuning use
OS timing and log a warning; see the TCP settings specification.
Folder and SFTP settings
Field
Kind
Default
Value or purpose
path
folder
Required
Existing readable directory; writable when used as a destination.
host
sftp
Required
Host name, IPv4 or IPv6 literal.
port
sftp
22
Integer, 1–65535.
username
sftp
Required
String, 1–255 characters.
auth.method
sftp
Required
password or key.
auth.password
sftp
Required for password auth
Secret reference.
auth.private_key
sftp
Required for key auth
Secret reference to an Ed25519, ECDSA or RSA private key.
auth.passphrase
sftp
Optional for key auth
Secret reference or null.
host_key_fingerprint
sftp
Required
SHA256: plus base64; pinned server key (Ed25519, ECDSA or RSA).
remote_directory
sftp
Required
Absolute remote path.
connect_timeout_ms
sftp
10000
Integer, 1–120,000.
operation_timeout_ms
sftp
30000
Integer, 1–600,000 per list/read/write operation.
mode
folder
watch
watch or poll.
poll_interval_seconds
Both
30 folder; 60 SFTP
Integer, 1–86,400; also the safety poll in folder watch mode.
file_pattern
Both
*
File-name glob using ? and *.
recursive
Both
false
Boolean; include subdirectories except the processed, filtered and invalid directories.
ignore_suffixes
Both
[".tmp", ".part", ".partial", ".crdownload"]
Array of file-name suffixes never read.
stable_seconds
Both
2
Integer, 0–3600; unchanged size and modification time before reading.
exclusive_open_check
folder
true
Boolean; also require exclusive read access before reading.
on_consumed
Both
move
move, delete, leave; after durable receipt.
processed_directory
Both
processed
Relative to source directory; created when needed (pdf_report sources add YYYY/MM/DD by local receipt date).
filtered_directory
Both
null
pdf_report sources with on_consumed=move: where a filtered report goes (under YYYY/MM/DD); null uses processed_directory. Relative, created when needed, different from the other two.
invalid_directory
Both
null
As filtered_directory, for a report that does not parse or is too large. With either set, a report is moved once it is filtered, invalid or routed.
write_mode
Both
atomic_rename
atomic_rename or direct.
Secret references are objects with a secret key naming the stored secret. Names match
^[a-z0-9][a-z0-9_.-]{0,62}$. Store values through Settings → Secrets in the console; never put values in
configuration. See secrets.
Channels
Fields below belong to each runtime channels entry. Every referenced endpoint must exist;
enabled channels require enabled endpoints. Sharing a serial or listener endpoint between
enabled channels produces a warning because only one channel can hold it at a time.
Common field
Default
Value or purpose
channel_id
Required
ID unique among channels.
label
Required
Display label.
kind
Required
bridge or message.
enabled
true
Boolean; false keeps the channel stopped.
tags
{}
Up to 20 string-to-string metadata entries.
Bridge fields
Field
Default
Value or purpose
endpoint_a, endpoint_b
Required
Different endpoint IDs; kinds serial, tcp_client, tcp_listener.
connection.connect_strategy
parallel
parallel, wait_for_listener_then_pair, receiver_then_sender. The listener strategy requires a listener and behaves as parallel.
connection.receiver
Required for receiver_then_sender
a or b; must be absent for other strategies.
connection.pairing_timeout_ms
5000
Integer greater than 0.
buffer.max_buffered_segments
1000
Integer greater than 0, per direction.
buffer.max_bytes
10485760
Integer greater than 0, per direction; both buffer limits apply.
buffer.overflow_action
block_then_degrade
Only block_then_degrade.
buffer.block_timeout_ms
5000
Integer greater than 0.
retry
Retry defaults below
Endpoint reconnect policy.
tap.framer
none
none, astm, hl7_mllp, au.
tap.record_messages
false
Boolean; storing observations requires a framer other than none.
tap.max_message_bytes
1048576
Integer, 1024–67,108,864.
tap.retention.max_age_days
30
Integer 1–36,500, or null for no age limit.
tap.retention.max_messages
null
Integer 1,000–1,000,000,000, or null for no count limit.
Tap retention applies to stored bridge observations, which have no deliveries. After startup
reconciliation and every ten minutes, the retention run purges the oldest recordings beyond
either limit. Setting both limits to null produces a retention_unbounded warning only
when tap.record_messages is true. See bridge tap behavior.
Retry policy fields
Used in channel retry and delivery retry objects. Delay grows by multiplier, capped
at max_delay_ms, with random variation of ±jitter_percent.
Field
Default
Value or purpose
initial_delay_ms
1000
Integer greater than 0.
max_delay_ms
60000
Integer at least initial_delay_ms.
multiplier
2.0
Number at least 1.0.
jitter_percent
20
Integer, 0–100.
max_consecutive_failures_before_alert
3
Integer greater than 0; bridge channels only, ignored for delivery retries.
Message fields and retention
Field
Default
Value or purpose
source
Required
Source connector below.
filters
[]
Ordered expressions; all must pass.
destinations
Required
1–20 destination connectors.
retry
Retry defaults above
Endpoint reconnect/reopen policy.
delivery
Delivery defaults below
Default policy for destinations.
retention.max_age_days
90
Integer, 1–36,500, or null for no age limit.
retention.max_messages
null
Integer, 1000–1,000,000,000, or null for no count limit.
Retention never purges undelivered or unresolved messages. Setting both limits to null
produces an unbounded-retention warning.
Connector fields
Field
Applies to
Default
Value or purpose
destination_id
Destination
Required
ID unique within the channel.
label
Destination
Required
Display label.
enabled
Destination
true
Boolean; disabled destinations get no new deliveries and queued deliveries wait.
endpoint
Both
Required
Endpoint ID.
protocol
Both
Required
Protocol compatible with the endpoint, below.
settings
Both
Per protocol
Protocol settings below.
duplicate_detection
Source
true
Boolean.
filters
Destination
[]
Expressions evaluated on the source message; all must pass.
mapping
Destination
null
Mapping object below; null passes through and requires the source protocol (hl7_file also passes an hl7_mllp source through).
delivery
Destination
Channel policy
Override individual delivery fields.
Protocol
Allowed endpoint kinds
Default / highest ack_required
astm, au
serial, tcp_client, tcp_listener
received / received; au class a: handed_off
hl7_mllp
tcp_client, tcp_listener
accepted / accepted; handed_off with ack_mode: none
delimited_file
folder, sftp
handed_off / handed_off
hl7_file
folder, sftp; destination only
handed_off / handed_off
pdf_report
folder, sftp; source only
—
Delivery policy fields
Field
Default
Value or purpose
max_attempts
5
Integer, 1–100 per attempt cycle; operator resend starts another cycle.
retry
Retry defaults above
Retry delays; bridge failure-alert threshold is ignored.
send_timeout_seconds
30
Integer, 1–3600 for the whole write or upload.
ack_timeout_seconds
30
Integer, 1–3600 after the last byte for the required acknowledgement.
ack_required
Per protocol above
handed_off, received, accepted; cannot exceed the protocol's highest level.
retry_unacknowledged
false
Boolean; enable only when the destination tolerates duplicate messages.
Protocol settings
Fields belong to source or destination connector settings.
ASTM (astm)
Field
Default
Value or purpose
charset
latin1
ascii, latin1, utf8.
role
computer
computer yields to instrument contention; instrument has priority.
ack_timeout_ms
15000
Integer, 1000–120,000.
receive_timeout_ms
30000
Integer, 1000–300,000.
max_frame_retries
6
Integer, 0–20.
max_frame_chars
240
Integer, 64–64,000; 240 is the E1381 limit, larger values are long frames.
contention_wait_ms
20000
Integer, 1000–60,000.
max_message_bytes
1048576
Integer, 1024–67,108,864.
AU (au)
Use the instrument's online parameter sheet. All fields are required except
block_timeout_ms and format.test_code_digits (2 or 3, default 2).
Field
Default
Value or purpose
profile
Required
au400, au640.
framing.start, framing.end
Required
Arrays of 1–2 control bytes, 1–31, excluding 6 and 21.
framing.bcc
Required
Boolean; XOR check byte.
framing.use_etb
Required
Boolean; only with framing.end set to [3].
framing.max_wire_len
Required
256, 512, 1024.
framing.class
Required
a (no receive ACK/NAK) or b (ACK after durable commit).
format.unit_no
Required
Boolean; incoming two-digit unit number.
format.rack_digits
Required
0, 4, 5.
format.sample_id_digits
Required
Integer, 1–20.
format.sex, format.age, format.month
Required
Boolean patient-header options.
format.patient_info_digits
Required
Array of six integers, each 0–20.
format.result_digits
Required
6, 9.
frame_timeout_ms
Required
Integer, 100–9900 in steps of 100.
block_timeout_ms
9900
Integer, 100–9900 in steps of 100; wait between blocks of an unfinished sample.
HL7 over MLLP (hl7_mllp)
Field
Default
Value or purpose
ack_mode
original
Source: original, enhanced. Destination also allows none, requiring ack_required=handed_off.
send_application_ack
true
Boolean; enhanced-mode source sends the requested application ACK after commit ACK.
Each at most 180 characters; generated MSH-3 through MSH-6.
processing_id
P
P, D, T.
charset
utf8
utf8, latin1, ascii.
max_message_bytes
1048576
Integer, 1024–67,108,864.
frame_timeout_ms
30000
Integer, 1000–300,000.
HL7 files (hl7_file)
Destination only: each delivery writes one HL7 v2 message as one file (segments ended by
carriage returns, UTF-8, no MLLP framing), for receivers that collect HL7 files from a folder or
SFTP server.
Field
Default
Value or purpose
file_name
Required
Template as for delimited files, for example ORU_{sample_id}_{date}{time}_{seq}.hl7.
Integer, 1024–67,108,864; a larger mapped message is not written (delivery failed, transform_error).
Delimited files (delimited_file)
Field
Default
Value or purpose
delimiter
,
One character: comma, semicolon, vertical bar or tab.
quote
Double quote
One character or null to disable quoting.
header_row
true
Boolean; read or write column headers.
skip_lines
0
Integer, 0–1000; leading lines ignored on read.
charset
utf8
utf8, latin1, ascii.
line_ending
crlf
Destination: crlf, lf.
write_bom
false
Boolean; destination only.
columns
Required
Non-empty array of columns below.
record_mode
one_per_line
one_per_line, grouped.
group_by
Required for grouped
Column name; consecutive equal values form one message.
max_file_bytes
20971520
Integer, 1024–1,073,741,824. Source: larger files are recorded as aborted, not read. Destination: a mapped file over the limit is not written (delivery failed, transform_error).
file_name
Required for destination
Template with no path separators. Variables: {message_id}, {control_id}, {sample_id}, {date}, {time}, {seq}; date is yyyyMMdd, time is HHmmss.
on_exists
suffix
Destination: suffix, overwrite, append, fail.
Column field
Default
Value or purpose
name
Required
Unique name matching ^[a-z][a-z0-9_]{0,40}$.
header
name
Case-insensitive source header match when header_row=true.
position
Next position
Integer at least 1; source without headers and destination order.
type
string
string, integer, decimal, date, datetime.
format
Required for date/datetime
Date/time format tokens listed below.
required
false
Boolean; source empty values make a message invalid.
The names control_id, sample_id, patient_id also populate message identifiers.
raw has no settings and is carried only by bridges, never message connectors.
PDF reports (pdf_report)
Source only: each born-digital report file is one message, read by a template of labelled
fields (PDF reports). Start from the shipped newborn screening
profile.
Field
Default
Value or purpose
max_file_bytes
20971520
Integer, 1024–268,435,456; a larger file is recorded as aborted, not read.
max_pages
20
Integer, 1–500.
phrase_gap
2
Number, 0.5–20, at most two decimals; a gap this many times the font size separates phrases.
label_area_end
[]
0–8 texts; the label area, where every word ending in : must be a declared label, ends at the line that begins with one.
fields
Required
1–200 fields below.
Field setting
Default
Value or purpose
name
Required
Unique name matching ^[a-z][a-z0-9_]{0,40}$; read as field.<name>.
label
Required
Label text, or an array of 1–8 alternatives.
position
right
right (on the label's line) or below (the block under the label).
occurrence
0
−1 to 20: which match of the label on a page; −1 the last.
line, phrase, indent
1, 0, 4
below only: block line (1–20), phrase of it (0–20, or −1 for the last), how far right of the label a line may start (0–600 points).
required
false
Boolean; the label and a value must be on page 1.
type, format
string, none
As delimited columns; date and datetime take one format or 1–4.
A report that does not match its template is stored invalid with a reason and a detail that
names the label or field. The names control_id, sample_id, patient_id also populate
message identifiers. Mappings read field.<name>, report.pages and report.file_base64
(the file in Base64, for embedding it in an HL7 ED value).
Filters and mappings
This is a field lookup; use the full transformation reference
for structure, escaping and error semantics. Occurrences and repetitions start at 0;
fields, components and subcomponents start at 1. AU fields are read-only.
Protocol
Path form
HL7
SEG[occ].field[rep].component.subcomponent
ASTM
R[occ].field[rep].component (record letters H P O R C Q M L)
AU
Header name or test[occ].name
Delimited file
col[occ].name
Current loop occurrence
$. plus field/component or field name; only inside for_each, append or a calculatefind.
Expression fields
Field or form
Default
Value or purpose
path, op
Required for comparison
Protocol path and operator below.
value
Per operator
String or number for text comparison; numeric operators require an exact decimal.
ignore_case
false
Boolean; applies to text comparisons and regular expressions.
all, any
Alternative expression form
Non-empty array of expressions.
not
Alternative expression form
One expression.
Operator
Required value
equals, not_equals, starts_with, contains
Text.
in, not_in
Non-empty array of text.
matches
Valid regular expression, at most 200 characters; anchor for a whole-value match.
exists, not_exists
No value.
gt, gte, lt, lte
Exact decimal; no exponent or thousands separator.
Use one comparison or one Boolean form per expression; nesting is limited to 32. Missing
fields read as empty text. Non-decimal field text fails every numeric comparison.
Mapping fields and rule operations
Field
Default
Value or purpose
tables
{}
Named code tables, each mapping strings to strings.
rules
Required
Ordered rule array; an HL7 or ASTM target of the same protocol starts as a copy of the source, otherwise output begins with generated protocol headers.
Rule op
Required fields
Optional fields and defaults
copy
from, to
default; required=false.
constant
value, to
None.
lookup
from, table, to
on_missing=error (error, keep, default, skip); default required only for on_missing=default; ignore_case=false.
concat
parts, to
parts: non-empty array of objects, each containing exactly one from path or text string.
Record names identify input/output occurrences; loops cannot nest.
sequence
to
start=1, integer 0–999,999,999; only inside for_each or append.
Date/time tokens are yyyy, yy (1970–2069), MM, dd, HH, mm, ss, which are
fixed-width, and M, d, H, which read one or two digits and must be followed by a
non-digit literal or end the format. Each component may appear only once per format; quote
literal letters with single quotes.
At least one token is required. See date and time formats.