Configuration field reference

Use this reference to look up fields while editing engine configuration. The configuration specification defines validation, apply behavior, path syntax and transformation rules in full.

bootstrap.json is read at engine start; restart after editing it. runtime.json is versioned and applied through the console or CLI. Unknown fields are rejected. Both files are UTF-8 JSON without comments. Durations use the unit in their name; sizes are bytes unless named _megabytes. Relative bootstrap paths resolve beside bootstrap.json.

In the tables, required means no default, assigned means the engine supplies it, and null is allowed only where shown. IDs match ^[a-z0-9][a-z0-9._-]{0,63}$; labels contain 1–100 characters. Keep IDs stable. Settings fields are relative to their named object, rather than complete JSON paths.

Bootstrap

Field Default Value or purpose
schema_version 1 Integer; supported schema version.
node.node_id Required ID; also used in the Windows pipe name.
node.display_name Required Display label.
node.environment prod dev, test, prod.
node.site_id null Optional string, at most 100 characters.
paths.state_directory Required Creatable, writable directory for stored messages, versions and IPC socket.
paths.log_directory <state_directory>/logs Creatable, writable directory.
ipc.path null Default: <state_directory>/packie.sock on Unix or \\.\pipe\packie-<node_id> on Windows. Custom Unix socket path: at most 100 bytes.
ipc.group packie Management access group on every platform. Unix: socket mode 0660 for the group. Windows: packie means local PACK-IE Operators; another name selects a local/domain group besides SYSTEM and Administrators. null or a missing group leaves service/administrator access only (Unix 0600); a missing group logs ipc.group_unavailable. Empty string is invalid.
hosting.shutdown_drain_seconds 15 Integer, 1–300; host stop timeout must allow at least this long.
runtime.file <state_directory>/runtime.json Runtime document; parent directory must be writable.
runtime.versions_kept null Keep all versions; otherwise a positive integer limits the count, preserving versions younger than audit.retention_days. Includes change records/sign-offs.
logging.level info error, warn, info, debug, trace.
logging.retention_days 30 Integer, 1–3650.
logging.rotate_at_megabytes 64 Integer, 1–1024; logs also rotate at local midnight.
logging.ring_buffer_events 20000 Integer, 1000–1,000,000; live in-memory log capacity.
diagnostics.snapshot_interval_seconds 1 Integer, 1–60.
diagnostics.retain_recent_errors 100 Integer, 10–10,000 per channel.
secrets.provider keystore (macOS, Windows); file (Linux) keystore or file. On Linux keystore needs a Secret Service (desktop session); without one the engine refuses to start and names file. The Linux package sets file.
secrets.file <state_directory>/secrets.json with provider=file Secret-store file path; created owner-only on the first secret write; on Unix, group and others must have no permission bits.
audit.retention_days 2190 Integer, 365–36,500. Removes whole sealed yearly audit files only after their newest event ages out; records the removal. Keep at least as long as the longest message retention and the lab's required calendar interval.
backup.directory Not set Backup root; required with a schedule. Each default/scheduled backup uses a new packie-backup-<UTC time> directory. Use an encrypted volume writable by the service account.
backup.schedule null No automatic backup; otherwise an object with daily_at and optional keep below.
backup.schedule.daily_at Required with schedule Local time HH:MM, daily. A time skipped by daylight saving runs at the next valid instant.
backup.schedule.keep 7 Integer, 1–365. After a scheduled backup, retain this many newest complete packie-backup-* directories; other names and pre-restore copies are untouched.
backup.stale_after_hours 26 with schedule, otherwise null Integer, 1–8760; backup_stale warns when the newest successful backup exceeds this age, or no backup succeeds within this interval after start. null without a schedule turns it off.
notifications.rate_limit_minutes 15 Integer, 1–1440; one notification per alert code/channel/endpoint/destination in this interval, shared by targets and by raise/clear events.
notifications.ca_file null Optional path to a PEM CA certificate bundle, read at startup; a relative path resolves against the bootstrap file's directory. SMTP adds these roots to bundled Mozilla roots; HTTPS webhooks use only this bundle when set. Unreadable/invalid bundles fail TLS sends.
notifications.email null SMTP target object; null disables e-mail.
notifications.email.host Required with e-mail Non-empty relay host name or address.
notifications.email.port Required with e-mail Integer, 1–65535.
notifications.email.security starttls starttls (usually 587), tls (usually 465) or none. none is allowed only for localhost, 127.0.0.1 or ::1. TLS verifies the relay certificate against bundled Mozilla roots plus notifications.ca_file when set.
notifications.email.username, notifications.email.password Not set Optional login; set both together. Password must be a secret reference, such as {"secret":"smtp-password"}.
notifications.email.from, notifications.email.to Required with e-mail Sender address and non-empty array of recipient addresses; each address needs one @ with text on both sides, without spaces or angle brackets.
notifications.email.severities ["warning","critical"] Non-empty subset of warning and critical.
notifications.webhook null Webhook target object; null disables it.
notifications.webhook.url Required with webhook HTTPS URL without a user name; HTTP allowed only for localhost, 127.0.0.1 or [::1]. Bundled Mozilla roots verify HTTPS certificates unless notifications.ca_file is set (then only that bundle is trusted); redirects are not followed.
notifications.webhook.bearer null Optional secret reference sent as Authorization: Bearer <secret>.
notifications.webhook.severities ["warning","critical"] Non-empty subset of warning and critical.
notifications.webhook.timeout_seconds 10 Integer, 1–60; time to connect and receive the response.
test_hooks false Boolean; scenario hooks. Never enable in production.

Backup paths resolve relative to the bootstrap directory like other bootstrap paths. See backup setup and restore and audit behavior. Notifications are off without targets. See notification relay setup for private-CA installation and service-account file access. Keep node/channel/endpoint labels free of patient information because notifications include them. See notification behavior and tests. Apply notes and verification references belong to commands, not fields in runtime.json: packie config apply <file> --note "Reason" and packie config verify <version> --note "Validation record reference" require 1–500 characters.

Runtime envelope and diagnostics

Field Default Value or purpose
schema_version 1 Integer; supported schema version.
config_version Assigned Successful apply increments the version. CLI apply uses an exported value to detect conflicting edits; it is not the new version number.
generated_at Assigned ISO-8601 UTC save time; informational.
diagnostics {} Overrides below.
alerts {} Thresholds below.
endpoints [] Endpoint definitions.
channels [] Channel definitions.
diagnostics.snapshot_interval_seconds Bootstrap value Integer, 1–60.
diagnostics.retain_recent_errors Bootstrap value Integer, 10–10,000 per channel.

Alert thresholds

All fields belong to runtime alerts and take integers. Zero disables only the thresholds marked “off”.

Field Default Range and alert
endpoint_down_seconds 60 1–86,400; endpoint-down warning.
endpoint_down_critical_seconds 900 At least endpoint_down_seconds; endpoint-down critical.
no_peer_seconds 0 (off) 0–86,400; no peer connected.
buffer_high_percent 80 1–100; bridge buffer pressure level.
buffer_high_seconds 10 1–3600; bridge buffer pressure duration.
delivery_backlog_count 1000 0–10,000,000 (0 off); queued delivery count.
delivery_backlog_age_seconds 300 0–604,800 (0 off); oldest queued delivery age.
delivery_attention_critical_count 10 1–10,000,000; deliveries needing attention become critical.
invalid_messages_count 5 0–10,000 (0 off); invalid messages in the window.
invalid_messages_window_seconds 600 1–86,400; invalid-message counting window.
disk_low_megabytes 1024 1–10,000,000; low-disk warning.
disk_critical_megabytes 256 1–disk_low_megabytes; low-disk critical.

Endpoints

Fields below belong to each entry in runtime endpoints. Kind-specific fields belong to that endpoint's settings.

Common field Default Value or purpose
endpoint_id Required ID unique among endpoints.
label Required Display label.
enabled true Boolean; false prevents opening the endpoint.
kind Required serial, tcp_client, tcp_listener, folder, sftp.
settings Required Object for the chosen kind.
tags {} Up to 20 string-to-string metadata entries.

Serial settings

Field Default Value or purpose
port_name Required Device path or COM port; unique among enabled endpoints, ignoring case.
baud_rate Required Integer greater than 0.
data_bits 8 5, 6, 7, 8.
parity none none, even, odd.
stop_bits one one, two.
flow_control none none, rts_cts, xon_xoff.
read_timeout_ms 1000 Integer, 1–60,000; read polling window, not a disconnect deadline.
write_timeout_ms 1000 Integer, 1–60,000; expiry fails the write attempt.
virtual_link null Unix pseudo-terminal path. When set, port_name must be virtual.

TCP settings

Field Kind Default Value or purpose
host tcp_client Required Host name, IPv4 or IPv6 literal.
bind_address tcp_listener Required IPv4 or IPv6 literal.
port Both Required Integer, 1–65535. Enabled listener binds must not overlap on the same port.
connect_timeout_ms tcp_client 5000 Integer, 1–120,000.
accept_backlog tcp_listener 16 Integer, 1–1024.
allowed_peer_cidrs tcp_listener [] IPv4/IPv6 CIDR strings; restrict accepted peers.
allow_any_peer tcp_listener false Boolean; explicitly set true to allow a non-loopback listener with no allowlist. Ignored with a non-empty allowlist.
idle_timeout_seconds Both 0 Integer, 0–604,800; 0 disables. Closes a connection idle in both directions.
keep_alive Both true Boolean; listener applies it to accepted sockets.
keep_alive_time_sec Both 30 Integer, 1–7200; idle time before first probe.
keep_alive_interval_sec Both 10 Integer, 1–3600; interval between probes.
keep_alive_retry_count Both 3 Integer, 1–100; unanswered probes before failure.

Probe settings apply when keep_alive=true. Older Windows hosts without probe tuning use OS timing and log a warning; see the TCP settings specification.

Folder and SFTP settings

Field Kind Default Value or purpose
path folder Required Existing readable directory; writable when used as a destination.
host sftp Required Host name, IPv4 or IPv6 literal.
port sftp 22 Integer, 1–65535.
username sftp Required String, 1–255 characters.
auth.method sftp Required password or key.
auth.password sftp Required for password auth Secret reference.
auth.private_key sftp Required for key auth Secret reference to an Ed25519, ECDSA or RSA private key.
auth.passphrase sftp Optional for key auth Secret reference or null.
host_key_fingerprint sftp Required SHA256: plus base64; pinned server key (Ed25519, ECDSA or RSA).
remote_directory sftp Required Absolute remote path.
connect_timeout_ms sftp 10000 Integer, 1–120,000.
operation_timeout_ms sftp 30000 Integer, 1–600,000 per list/read/write operation.
mode folder watch watch or poll.
poll_interval_seconds Both 30 folder; 60 SFTP Integer, 1–86,400; also the safety poll in folder watch mode.
file_pattern Both * File-name glob using ? and *.
recursive Both false Boolean; include subdirectories except the processed, filtered and invalid directories.
ignore_suffixes Both [".tmp", ".part", ".partial", ".crdownload"] Array of file-name suffixes never read.
stable_seconds Both 2 Integer, 0–3600; unchanged size and modification time before reading.
exclusive_open_check folder true Boolean; also require exclusive read access before reading.
on_consumed Both move move, delete, leave; after durable receipt.
processed_directory Both processed Relative to source directory; created when needed (pdf_report sources add YYYY/MM/DD by local receipt date).
filtered_directory Both null pdf_report sources with on_consumed=move: where a filtered report goes (under YYYY/MM/DD); null uses processed_directory. Relative, created when needed, different from the other two.
invalid_directory Both null As filtered_directory, for a report that does not parse or is too large. With either set, a report is moved once it is filtered, invalid or routed.
write_mode Both atomic_rename atomic_rename or direct.

Secret references are objects with a secret key naming the stored secret. Names match ^[a-z0-9][a-z0-9_.-]{0,62}$. Store values through Settings → Secrets in the console; never put values in configuration. See secrets.

Channels

Fields below belong to each runtime channels entry. Every referenced endpoint must exist; enabled channels require enabled endpoints. Sharing a serial or listener endpoint between enabled channels produces a warning because only one channel can hold it at a time.

Common field Default Value or purpose
channel_id Required ID unique among channels.
label Required Display label.
kind Required bridge or message.
enabled true Boolean; false keeps the channel stopped.
tags {} Up to 20 string-to-string metadata entries.

Bridge fields

Field Default Value or purpose
endpoint_a, endpoint_b Required Different endpoint IDs; kinds serial, tcp_client, tcp_listener.
connection.connect_strategy parallel parallel, wait_for_listener_then_pair, receiver_then_sender. The listener strategy requires a listener and behaves as parallel.
connection.receiver Required for receiver_then_sender a or b; must be absent for other strategies.
connection.pairing_timeout_ms 5000 Integer greater than 0.
buffer.max_buffered_segments 1000 Integer greater than 0, per direction.
buffer.max_bytes 10485760 Integer greater than 0, per direction; both buffer limits apply.
buffer.overflow_action block_then_degrade Only block_then_degrade.
buffer.block_timeout_ms 5000 Integer greater than 0.
retry Retry defaults below Endpoint reconnect policy.
tap.framer none none, astm, hl7_mllp, au.
tap.record_messages false Boolean; storing observations requires a framer other than none.
tap.max_message_bytes 1048576 Integer, 1024–67,108,864.
tap.retention.max_age_days 30 Integer 1–36,500, or null for no age limit.
tap.retention.max_messages null Integer 1,000–1,000,000,000, or null for no count limit.

Tap retention applies to stored bridge observations, which have no deliveries. After startup reconciliation and every ten minutes, the retention run purges the oldest recordings beyond either limit. Setting both limits to null produces a retention_unbounded warning only when tap.record_messages is true. See bridge tap behavior.

Retry policy fields

Used in channel retry and delivery retry objects. Delay grows by multiplier, capped at max_delay_ms, with random variation of ±jitter_percent.

Field Default Value or purpose
initial_delay_ms 1000 Integer greater than 0.
max_delay_ms 60000 Integer at least initial_delay_ms.
multiplier 2.0 Number at least 1.0.
jitter_percent 20 Integer, 0–100.
max_consecutive_failures_before_alert 3 Integer greater than 0; bridge channels only, ignored for delivery retries.

Message fields and retention

Field Default Value or purpose
source Required Source connector below.
filters [] Ordered expressions; all must pass.
destinations Required 1–20 destination connectors.
retry Retry defaults above Endpoint reconnect/reopen policy.
delivery Delivery defaults below Default policy for destinations.
retention.max_age_days 90 Integer, 1–36,500, or null for no age limit.
retention.max_messages null Integer, 1000–1,000,000,000, or null for no count limit.

Retention never purges undelivered or unresolved messages. Setting both limits to null produces an unbounded-retention warning.

Connector fields

Field Applies to Default Value or purpose
destination_id Destination Required ID unique within the channel.
label Destination Required Display label.
enabled Destination true Boolean; disabled destinations get no new deliveries and queued deliveries wait.
endpoint Both Required Endpoint ID.
protocol Both Required Protocol compatible with the endpoint, below.
settings Both Per protocol Protocol settings below.
duplicate_detection Source true Boolean.
filters Destination [] Expressions evaluated on the source message; all must pass.
mapping Destination null Mapping object below; null passes through and requires the source protocol (hl7_file also passes an hl7_mllp source through).
delivery Destination Channel policy Override individual delivery fields.
Protocol Allowed endpoint kinds Default / highest ack_required
astm, au serial, tcp_client, tcp_listener received / received; au class a: handed_off
hl7_mllp tcp_client, tcp_listener accepted / accepted; handed_off with ack_mode: none
delimited_file folder, sftp handed_off / handed_off
hl7_file folder, sftp; destination only handed_off / handed_off
pdf_report folder, sftp; source only —

Delivery policy fields

Field Default Value or purpose
max_attempts 5 Integer, 1–100 per attempt cycle; operator resend starts another cycle.
retry Retry defaults above Retry delays; bridge failure-alert threshold is ignored.
send_timeout_seconds 30 Integer, 1–3600 for the whole write or upload.
ack_timeout_seconds 30 Integer, 1–3600 after the last byte for the required acknowledgement.
ack_required Per protocol above handed_off, received, accepted; cannot exceed the protocol's highest level.
retry_unacknowledged false Boolean; enable only when the destination tolerates duplicate messages.

Protocol settings

Fields belong to source or destination connector settings.

ASTM (astm)

Field Default Value or purpose
charset latin1 ascii, latin1, utf8.
role computer computer yields to instrument contention; instrument has priority.
ack_timeout_ms 15000 Integer, 1000–120,000.
receive_timeout_ms 30000 Integer, 1000–300,000.
max_frame_retries 6 Integer, 0–20.
max_frame_chars 240 Integer, 64–64,000; 240 is the E1381 limit, larger values are long frames.
contention_wait_ms 20000 Integer, 1000–60,000.
max_message_bytes 1048576 Integer, 1024–67,108,864.

AU (au)

Use the instrument's online parameter sheet. All fields are required except block_timeout_ms and format.test_code_digits (2 or 3, default 2).

Field Default Value or purpose
profile Required au400, au640.
framing.start, framing.end Required Arrays of 1–2 control bytes, 1–31, excluding 6 and 21.
framing.bcc Required Boolean; XOR check byte.
framing.use_etb Required Boolean; only with framing.end set to [3].
framing.max_wire_len Required 256, 512, 1024.
framing.class Required a (no receive ACK/NAK) or b (ACK after durable commit).
format.unit_no Required Boolean; incoming two-digit unit number.
format.rack_digits Required 0, 4, 5.
format.sample_id_digits Required Integer, 1–20.
format.sex, format.age, format.month Required Boolean patient-header options.
format.patient_info_digits Required Array of six integers, each 0–20.
format.result_digits Required 6, 9.
frame_timeout_ms Required Integer, 100–9900 in steps of 100.
block_timeout_ms 9900 Integer, 100–9900 in steps of 100; wait between blocks of an unfinished sample.

HL7 over MLLP (hl7_mllp)

Field Default Value or purpose
ack_mode original Source: original, enhanced. Destination also allows none, requiring ack_required=handed_off.
send_application_ack true Boolean; enhanced-mode source sends the requested application ACK after commit ACK.
version 2.5.1 2.x or 2.x.y; generated MSH-12.
sending_application, sending_facility, receiving_application, receiving_facility Empty string Each at most 180 characters; generated MSH-3 through MSH-6.
processing_id P P, D, T.
charset utf8 utf8, latin1, ascii.
max_message_bytes 1048576 Integer, 1024–67,108,864.
frame_timeout_ms 30000 Integer, 1000–300,000.

HL7 files (hl7_file)

Destination only: each delivery writes one HL7 v2 message as one file (segments ended by carriage returns, UTF-8, no MLLP framing), for receivers that collect HL7 files from a folder or SFTP server.

Field Default Value or purpose
file_name Required Template as for delimited files, for example ORU_{sample_id}_{date}{time}_{seq}.hl7.
on_exists suffix suffix, overwrite, fail.
version, sending_application, sending_facility, receiving_application, receiving_facility, processing_id As hl7_mllp Generated MSH-12, MSH-3 through MSH-6 and MSH-11.
max_message_bytes 1048576 Integer, 1024–67,108,864; a larger mapped message is not written (delivery failed, transform_error).

Delimited files (delimited_file)

Field Default Value or purpose
delimiter , One character: comma, semicolon, vertical bar or tab.
quote Double quote One character or null to disable quoting.
header_row true Boolean; read or write column headers.
skip_lines 0 Integer, 0–1000; leading lines ignored on read.
charset utf8 utf8, latin1, ascii.
line_ending crlf Destination: crlf, lf.
write_bom false Boolean; destination only.
columns Required Non-empty array of columns below.
record_mode one_per_line one_per_line, grouped.
group_by Required for grouped Column name; consecutive equal values form one message.
max_file_bytes 20971520 Integer, 1024–1,073,741,824. Source: larger files are recorded as aborted, not read. Destination: a mapped file over the limit is not written (delivery failed, transform_error).
file_name Required for destination Template with no path separators. Variables: {message_id}, {control_id}, {sample_id}, {date}, {time}, {seq}; date is yyyyMMdd, time is HHmmss.
on_exists suffix Destination: suffix, overwrite, append, fail.
Column field Default Value or purpose
name Required Unique name matching ^[a-z][a-z0-9_]{0,40}$.
header name Case-insensitive source header match when header_row=true.
position Next position Integer at least 1; source without headers and destination order.
type string string, integer, decimal, date, datetime.
format Required for date/datetime Date/time format tokens listed below.
required false Boolean; source empty values make a message invalid.

The names control_id, sample_id, patient_id also populate message identifiers. raw has no settings and is carried only by bridges, never message connectors.

PDF reports (pdf_report)

Source only: each born-digital report file is one message, read by a template of labelled fields (PDF reports). Start from the shipped newborn screening profile.

Field Default Value or purpose
max_file_bytes 20971520 Integer, 1024–268,435,456; a larger file is recorded as aborted, not read.
max_pages 20 Integer, 1–500.
phrase_gap 2 Number, 0.5–20, at most two decimals; a gap this many times the font size separates phrases.
label_area_end [] 0–8 texts; the label area, where every word ending in : must be a declared label, ends at the line that begins with one.
fields Required 1–200 fields below.
Field setting Default Value or purpose
name Required Unique name matching ^[a-z][a-z0-9_]{0,40}$; read as field.<name>.
label Required Label text, or an array of 1–8 alternatives.
position right right (on the label's line) or below (the block under the label).
occurrence 0 −1 to 20: which match of the label on a page; −1 the last.
line, phrase, indent 1, 0, 4 below only: block line (1–20), phrase of it (0–20, or −1 for the last), how far right of the label a line may start (0–600 points).
required false Boolean; the label and a value must be on page 1.
type, format string, none As delimited columns; date and datetime take one format or 1–4.

A report that does not match its template is stored invalid with a reason and a detail that names the label or field. The names control_id, sample_id, patient_id also populate message identifiers. Mappings read field.<name>, report.pages and report.file_base64 (the file in Base64, for embedding it in an HL7 ED value).

Filters and mappings

This is a field lookup; use the full transformation reference for structure, escaping and error semantics. Occurrences and repetitions start at 0; fields, components and subcomponents start at 1. AU fields are read-only.

Protocol Path form
HL7 SEG[occ].field[rep].component.subcomponent
ASTM R[occ].field[rep].component (record letters H P O R C Q M L)
AU Header name or test[occ].name
Delimited file col[occ].name
Current loop occurrence $. plus field/component or field name; only inside for_each, append or a calculate find.

Expression fields

Field or form Default Value or purpose
path, op Required for comparison Protocol path and operator below.
value Per operator String or number for text comparison; numeric operators require an exact decimal.
ignore_case false Boolean; applies to text comparisons and regular expressions.
all, any Alternative expression form Non-empty array of expressions.
not Alternative expression form One expression.
Operator Required value
equals, not_equals, starts_with, contains Text.
in, not_in Non-empty array of text.
matches Valid regular expression, at most 200 characters; anchor for a whole-value match.
exists, not_exists No value.
gt, gte, lt, lte Exact decimal; no exponent or thousands separator.

Use one comparison or one Boolean form per expression; nesting is limited to 32. Missing fields read as empty text. Non-decimal field text fails every numeric comparison.

Mapping fields and rule operations

Field Default Value or purpose
tables {} Named code tables, each mapping strings to strings.
rules Required Ordered rule array; an HL7 or ASTM target of the same protocol starts as a copy of the source, otherwise output begins with generated protocol headers.
Rule op Required fields Optional fields and defaults
copy from, to default; required=false.
constant value, to None.
lookup from, table, to on_missing=error (error, keep, default, skip); default required only for on_missing=default; ignore_case=false.
concat parts, to parts: non-empty array of objects, each containing exactly one from path or text string.
datetime from, to, input, output from_timezone, to_timezone: IANA names; conversion requires both.
when condition, then else; branches contain rule arrays.
for_each over, into, rules Record names identify input/output occurrences; loops cannot nest.
sequence to start=1, integer 0–999,999,999; only inside for_each or append.

Date/time tokens are yyyy, yy (1970–2069), MM, dd, HH, mm, ss, which are fixed-width, and M, d, H, which read one or two digits and must be followed by a non-digit literal or end the format. Each component may appear only once per format; quote literal letters with single quotes. At least one token is required. See date and time formats.